Selasa, 07 November 2023

Settingan parameter DEH Spinning L-2 Lt-7 TIC yokogawa UT350

Alternatif PID
P = 5.0
I = 240
D = 60

Masuk ke parameter 1
Tekan dan tahan tombol "SET/ENT" Sampai muncul "oP.Pa" lalu tekan "SET/ENT" sekali lagi.

LL = on
A1 = 235.0
A2 = 226.0
A3 = 240.0
At = off
SC = off
SP.no = 1
PId = 1Gr
1.P = 3.4
1.I = 74
1.d = 18
FL = 0.0
bS = 0.0
UPr = off
dnr = off
oH = 100
oL = 0.0
dr = 0
orb = 5.0
orH = 100.0
orL = 0.0
or = 0.0
1.SP = 230.0
2.SP = 0.0
3.SP = 0.0
4.SP = 0.0

Masuk ke parameter 2
Tekan dan tahan tombol "SET/ENT" Sampai muncul "oP.Pa" lalu tekan panah "^" sampai muncul "StUP" lalu tekan "SET/ENT"

Pwd = 0
SPH = 100.0
SPL = 0.0
AL1 = 1
AL2 = 2
AL3 = 1
HY1 = 0.0
HY2 = 0.0
HY3 = 0.0
dY1 = 0.00
dY2 = 0.00
dY3 = 0.00
Ct = 30
Po = 0.0
C.md = 0
Eon = off
Ar = AUto
tmU = 0
tESt = 0

Masuk ke parameter 3
Tekan dan tahan tombol "SET/ENT" Sampai muncul "oP.Pa" lalu tekan panah "^" sampai muncul "StUP" lalu tekan "SET/ENT"
Tekan "SET/ENT" sekali lagi sampai muncul "FUnC" tekan panah "^" akan muncul "I/o" lalu tekan "SET/ENT" sekali

In = 3 (thermo couple)
Unit = °C
rH = 500.0
rL = 0.00
rJC = on
bSL = 1
oT = 1 (1-10v)
rEt = 1
rtH = 500.0
rtL = 0.0
diS = 1
C.S1 = off
C.S2 = off
C.S3 = off
C.S4 = off
LoCY = off
Pwd = 0

Sekian dan terimakasih